FCL (General)shoichi.oshino - 12:05 Wednesday 25 March 2026 (36652)
Print this reportAir Conditioner Failure in the computer roomHayakawa-san reports that an unusual noise is coming from the outdoor unit of the No. 2 air conditioner in the computer room. Checking the temperature in the computer room, it has risen from the normal 22 to 25 degrees. In addition, the discharge temperature of the No. 2 air conditioner is almost the same as the room temperature. Hayakawa-san is now contacting the vendor to ask for the repair of the air conditioner. The room temperature has been holding at around 25 degrees for the past 12 hours.
Images attached to this report
Comments to this report:
shoichi.oshino - 14:17 Monday 30 March 2026 (36673)
Print this reportAs a temporary measure carried out by the company, Air Conditioning Unit No. 2 began blowing cool air. In addition, the room temperature decreased to around 22 degrees. However, since the compressor of Unit No. 2 has deteriorated, it was decided to install a new air conditioning unit.