DGS (General)
takahiro.yamamoto - 12:44 Sunday 09 February 2025 (32620) Print this report
Comment to Update model files (32617)

I heard that the local dump part would be moved to the NB side, but it appears that the ISC part was actually moved to the DCUID which was used for NB.

Now many scripts and pipelines are unavailable due to the update of Type-A models.
Just ones I am currently aware are as following.
- Online state vector by k1detdq
- Segment file related to overflows
- Lockloss guardian
- DARM calibration scripts

In addition to that, I found some incomplete build as follows.
- Confusion of sender/receiver on ITMX as shown in Fig.1
- Wrong IPC rate for NBDAMP on ITMY as shown in Fig.2
- Remaining old info. about NBDAMP on ETMY as shown in Fig.3
- Mixing of old and new sender info about NBDAMP on ETMY as shown in Fig.4
- Wrong IPC rate for {PF,MN,TM}OPLEVs for all 4 type-As as shown in Fig.5-7
- Remaining old sender info. on CALCS as shown in Fig.8

I'm not sure the control signals can be sent/received among real-time models properly.
The only way to get back reliable IPC communications is to rebuild and restart them after cleaning up K1.ipc.
I think removing these chaos and unreliable situation is the most urgent task in next (a couple of?) weeks.

Images attached to this comment