FCL (Air)
shinji.miyoki - 22:24 Friday 26 December 2025 (35984) Print this report
Temp Adjustment

Because stopping the cryocoolers for duct shields at all area, the heater powers were adjusted at each station.

  • Corner station: change rthe setting temp from 18 to 21 for the precision cooler near SR2.
  • X end station:  Heater power from 0 to 900W.
  • Y end station: No adjustment at present.
Comments to this report:
shinji.miyoki - 21:48 Monday 29 December 2025 (36001) Print this report

I added heater power by 600W at EYC 1F to increase the temp in the EYC area around 22:00.

shinji.miyoki - 23:10 Monday 05 January 2026 (36026) Print this report

[Kimura, Yasui, Miyoki]

We adjusted the heat generation condition in {IE}{XY}V because TMPs and dry pumps were off, and ion pumps were on at each V area.

  • IXV: Off the ceilling light, 1 FFU operation, Air conditioner off, 900W in Delonghi heater.
  • EXV: Off the ceilling light, 2 FFUs operation, Air conditioner off, 600W in Delonghi heater.
  • EYV: Off the ceilling light, 2 FFUs operation, Air conditioner off, 900W in Delonghi heater.
  • IYV: On the ceilling light, 2 FFUs operation,  Air conditioner on, 600W in Delonghi heater.

At present, I cannot know the precise temp data at IYV maybe because of no battery in the Ondotori. 

In addition, I set the target temp of the precision cooler near SR2 from 20 to 18 to compensate the heat from 7 TMPs and dry pumps operation. in the corner station. Also I turned off the ceilling light above IMC.