Reports 1-1 of 1 Clear search Modify search
DGS (General)
takahiro.yamamoto - 2:06 Tuesday 18 September 2018 (6174) Print this report
IO chassis for LSC died
I found the all real-time models on k1lsc0 died today. (FE in the STATE_WORD turned red.)

I tried to restore the models by re-starting models and rebooting the real-time front-end.
But the models were not restored and RTFE was not able to find the IO chassis.

I also checked HIB card on the IO chassis but the indicator did not turn green after the RTFE booted up.
So HIB card on the IO chassis may be broken...

I will try to cold-boot the RTFE and the IO chassis tomorrow.
Comments to this report:
takahiro.yamamoto - 18:40 Tuesday 18 September 2018 (6179) Print this report
k1lsc0 booted up by replacing the HIB card on IO chassis.
The boot-up test was conducted w/o the Dolphin connection in order to avoid stopping another models.

I will reconnect and k1lsc0 to the Dolphin network and reboot it after today's commissioning tasks will be finished.