Electrical Cable Outlet Heatup at TMSX

[miyoki, hayakawa, takahashim, sawadah, YamaT, Ikeda, Yokozawa]

Kimura-san found the hotspot at the electrical cable outlet of the table tap that was extended into the TMSX DGS rack as photo1 and 2. His thermographic meter measured roughly 80 °C. 

The total current used for these two taps (one shows the hotspot) was ~ 7 A, which was well below the limit of 15A. So,  we suspected that there were some troubles with this tap, plug, and/or their contact. Anyway, we removed this tap and  plug, and improved the electrical cable connection at this point.

During this activity, we needed to turn off the Kikusui power supplies inside the TMSX DGS rack, a data logger, PEM instruments, and some electronics inside the TMSX optical layout housing.

Images attached to this report
Comments to this report:
takahiro.yamamoto - 23:15 Wednesday 18 November 2026 (37877) Print this report
[Yokozawa, Ikeda, Sawada, Takahashi, Yamaguchi, Hayakawa, Ohmae, YamaT]

We replaced the power outlet that had been reported as problematic with a power strip (Fig.1) that plugs directly into the circuit breaker (Fig.2).

Because it was necessary to power down all equipment during the replacement, we powered down the four PDs on the TMSX optical table, the PEM BOX power supply, the circuits inside the TMSX rack, two DC18V power supply units, and the power switch of the data logger for polarization measurement. Note that since the IO chassis was not shut down in this time, we didn't restart the real-time models and the front-end server.

After the replacement, we restored power to all systems, checked the response of four PDs with a work light, and then completed this work.

-----
The problematic plug of the power strip felt only slightly warm to the touch (40–50degC?) so it seems a bit strange that 80degC was measured in previous investigation. I thought it was measuring the surface temperature through radiation, but was it able to measure the internal temperature?

The removed plug showed discoloration on the contact surface with the outlet (Fig.3) same as the handle of plug, but there were no signs of burning, and a visual inspection of the interior of the outlet revealed no problems (Fig.4).

Regarding the PDs that should be shut down when power is cut off, the layout diagram did not include PDs for the polarized monitor.
Has Mirror Map information no longer been updated?
Images attached to this comment
nobuhiro.kimura - 20:51 Thursday 19 November 2026 (37888) Print this report

[Kimura and Yasui]
 For reference, we present images of the heat-generating area taken with an infrared camera and a standard camera.
(Photo 1 and Photo 2)
 Photo 1, taken with an infrared camera, shows that the temperature of the hotspot is 76.3°C.
This area is where the metal conductor of the plug connects to the metal conductor of the receptacle inside the outlet.
Photo 1 clearly shows that this is the area generating the most heat. 
 In Photo 2, discoloration of the plastic insulator on the plug’s surface—presumed to be caused by this heat—is visible.
 
 Photo 3 is an infrared image of an office power strip inside a DGS rack with a Kikusui power supply plug inserted.
From Photo 3, it can be seen that the temperature at the plug insertion point is 27.3°C, indicating that the heat generated is only slightly warmer than room temperature.

 Photo 4 shows an infrared image taken after the overheating outlet was removed and the Kikusui power supply inside the DGS rack was reconnected via a circuit breaker.
Photo 4 shows that the temperature of the circuit within the circuit breaker is 31.7°C, indicating that the temperature has dropped compared to before the outlet was removed.

 Photo 5 is an infrared image of the outlet in the DGS rack where the Kikusui power supply’s plug is inserted after the circuit breaker shown in Photo 4 was installed.
Photo 5 shows that the temperature at the plug insertion point is 23.6°C, indicating a decrease of approximately 4°C compared to the temperature shown in Photo 3.
 

Images attached to this comment
nobuhiro.kimura - 8:11 Friday 20 November 2026 (37892) Print this report

[Kimura

 According to the manufacturer, the recommended replacement interval for OA taps is 3 to 4 years, and they should be inspected about once a year.
In addition, loosening of the plug connection is said to cause overheating.
This loosening appears to be caused by bending of the plug connection point, among other factors.

 Since some OA taps at KAGRA have exceeded their recommended replacement interval, we recommend conducting a comprehensive inspection.