[miyoki, hayakawa, takahashim, sawadah, YamaT, Ikeda, Yokozawa]
Kimura-san found the hotspot at the electrical cable outlet of the table tap that was extended into the TMSX DGS rack as photo1 and 2. His thermographic meter measured roughly 80 °C.
The total current used for these two taps (one shows the hotspot) was ~ 7 A, which was well below the limit of 15A. So, we suspected that there were some troubles with this tap, plug, and/or their contact. Anyway, we removed this tap and plug, and improved the electrical cable connection at this point.
During this activity, we needed to turn off the Kikusui power supplies inside the TMSX DGS rack, a data logger, PEM instruments, and some electronics inside the TMSX optical layout housing.