shinji.miyoki - 6:54 Tuesday 22 September 2026 (37506) Print this report
Power Outage

[Power outage]

According to the auto mail system for the electrical system trouble,

The power outage happened at 2026/09/21 18:08:16,  and its recovery was at 2026/09/21 18:09:18.

Almost a 1-minute power outage. This is consistent with the report from an IPMU member via e-mail about the power outage at the IPMU building and the Kamioka Complex Building.

 

[Electricity Recovery Situation]

Atotsu Koguchi: still no electricity. According to Nakai-denki-san, Only the cubicle at the Atotsu entrance has no automatic recovery function, while other cubicles at EY end and the corner have it. It is quite strange design. Anyway, Uchiyama-kun, Oshino-kun, and Nakai-denki-san will go to the Atotsu entrance around 8:00 for recovery. Also Fukumura-san will be at the DAB.

Actually, no network and no webcam images, no warning system, no PHS, and no dry air are available at the Atotsu entrance after some of them were alive because of a battery.

Other places (Corner XY ends): recovered.

 

[Auto action after the power outage and to dos]

  • All GVs were closed.
  • All pumps seemed to stop. All TMPs except for SRM had an interlock system. The TMP/DRY for SRM has no interlock system, but the GV between the TMP and dry pump is expected to close due to its fail-safe system.
  • Ion pumps are also expected to stop because of a 1-minute power outage. 
  • Cryocoolers and their water-supplying system seem to have stopped. We can verify this with webcam images. Vacuum level in each cryostat (IXC, IYC, EYC) is expected to worsen because of the temperature increase of the duct shields.
  • The precision coolers for the PSL room and BS area seem to be automatically recovered, and we verified their operation by web cameras. However, the target temperature seems to be changing from the set values. ~21C is expected for the PSL room, but 23.7C at present. 18C for BS, but 22 at present. 23.7C for the PSL room should be set back at ~ 21:00 again before restarting the IR laser.
  • Green lasers seem to be operating due to the batteries. The IR laser seems to have stopped. The water chiller also stopped, according to the image of webcamers. The water chiller system for beam dumpers are also expected to stop. So we need to restart it when the IR laser is recovered.
  • The water supply system seemed to have recovered automatically by webcam, and the fact that the precission coolers are working well.
  • Dehumidifiers (Corner station and TMP area): All seemed to stop. We need to restart manually.
  • Coolers
    • Corner
      • Daikin coolers at MCF, BS, SRM, and the Corner Machine room seemed to stop. They can be restarted by switching to be off, then to the cooling mode again. 
      • Daikin cooler at IYC stopped originally.
      • Hitachi cooler at IYV: I guess it stopped. We need to restart it.
      • Hitachi cooler at IYX: It originally stopped.
    • Ends
      • EXC:  I guess it stopped. We need to restart one, not two.
      • EXV: It originally stopped.
      • EYC: It originally stopped.
      • EYV: It originally stopped.
  • Heaters in each area
    • Corner
      • MCF(Delonghi): stopped. We need to turn it on manually.
      • PR2(Sunrise): stopped. I checked its response and turned it off again.
      • IXV, IYV (Delonghi): stopped. We need to turn it on manually.
      • Others (PR3, BS, SR3) stopped originally.
    • Ends
      • EYV (Sunrise): stopped. I recovered it at level 1
      • EYC (2 x Sunrise): stopped. I recovered it at level 2
      • EYC (Delonghi): stopped. We need to turn it on manually.
      • EXV (Delonghi): stopped. We need to turn it on manually.
      • EXC (Sunrise) : stopped originally
  • DGS/DMG system
    • Coolers in the control room in DAB: stopped and 40C dgrees before turning on coolers by Ohino-kun and Washimi-kun.
    • Coolers in the computer room in KAGRA: They seemed to stop. Some of the DAQ and DMG systems kept working. So the temperature is now gradually increasing. Ikeda-san tried to stop several systems. DMG system kept working.
Comments to this report:
shinji.miyoki - 7:44 Tuesday 22 September 2026 (37507) Print this report

Data from the Hokuriku power line company.

Images attached to this comment
takashi.uchiyama - 15:56 Tuesday 22 September 2026 (37508) Print this report
2026/09/22
Hayakawa, KImura(remote), Uchiyama

We restarted TMPs at the KAGRA site. (#Number means the unit number of pumping units in the figure)
- The center area
IMC#1, IFI#9, PR2-BS#11, BS-SR2#12, SR2-SR3#4, SRM#14, BS-GVbsx#3, GVbsx-IXC#5, IXA#7, BS-GVbsy#13, GVbsy-IYC#6, IYA#40, IXC-IXA#7, IYC-IYA#8.
- 5 TMPs in the Xarm tunnel
- 5 TMPs in the Yarm tunnel
- The EYC area
EYA-GVey#34, EYA-EYC#35, EYA-EYC#38, EYC-TMSY#36, TMSY#26
Note that GVtmsy was closed.

We noticed the ion pumps at IXV and at EYV were operating. We turned them off.

When we restored the TMP at SRM in the morning, we forgot to open GVommt. This afternoon, we opened GVommt, and the vacuum pressure level in the OMC area improved.



Images attached to this comment
takashi.uchiyama - 9:41 Wednesday 23 September 2026 (37514) Print this report
2026/09/23

Attached figure shows the current vacuum pressure distribution at 9:31 on 23rd September.
Vacuum pressure is recovered except for IXC, IYC, and EYC.
Images attached to this comment
takashi.uchiyama - 11:08 Wednesday 23 September 2026 (37515) Print this report
2026/09/23

I paused vacuum alert for the following channels in addition to GV_ETMX,
X_EXGV, X_EXA1, X_EXA2, X_EXC, X_EXT.
Images attached to this comment
takahiro.yamamoto - 12:38 Wednesday 23 September 2026 (37516) Print this report
X2700 and Y2100 show a negative value because one of MOXA/Saba-taro which is proto-type of a new MOXA/Saba-taro system is now unreachable.
X2700 and Y2100 aren't used for any interlock and situation at them should be not so bad according to readout values at X1500, X3000, Y1500, and Y3000.
So recovering them doesn't seem to be so urgent.
But please be careful absolute of readout values at these two CC-10 represent pressure values when MOXA/Saba-taro was reachable in last time (probably before blackout)
and please check MOXA/Saba-taro after recovering works for other urgent equipment will be finished.