VAC (EX)takaaki.yokozawa - 6:31 Thursday 20 August 2026 (37387)
Print this reportETMX GV closedI found ETMX GV was closed around 2:00 a.m. today
Images attached to this report
Comments to this report:
takashi.uchiyama - 8:32 Thursday 20 August 2026 (37388)
Print this reportI put several figures.
Fig. 1: Vacuum pressure distribution at 8:22, 20 August, 2026. Fig. 2: current temperature distribution of the duct shield. Fig. 3: Vacuum pressure trend around EX.
Vacuum pressure at X_30 reached 1E-3Pa at 2:38, 20 August, 2026 and GV_etmx was closed by the interlock system. After closing the GV, vacuum pressure level was recovered. Since the current temperature of the EX duct shields are more than 180 K, water evaporation seems to be completed.
We think that we can open the GV again.
Images attached to this comment
takashi.uchiyama - 9:48 Thursday 20 August 2026 (37389)
Print this reportNakagaki, Sawada