DGS (General)takahiro.yamamoto - 12:56 Monday 14 April 2025 (33397)
Print this reportComment to Trouble shooting mcf0 machine (33348)I did an on-site inspection and I couldn't find any strangeness. But MCF couldn't be recovered yet though I tried to reboot, cold-boot, etc. I thought replacing HIB card is a thing we should do at first. Remaining works can be done in parallel with IFO works because it's now related to the power sources and IMC SAFE is not required.
----- Check log - DC24V is served properly from the power source according to a check by multimeter - DC3V, 5V, and 12V are properly provided on the mother board according to a check by multimeter. - Timing Slave seems to be synchronized according to an indicator on the front panels of Timing Slave and Fanout. - ADC and DAC seems to be launched according to an indicator on each board. - HIB card also seems to have no problem according to an indicator on the board.
Concerns All AI output cables were not screwed and a GND pin side of some of them were half unplugged. I'm not sure it's a cause of this problem. But such kind of usages can make troubles on electronics. Note that "Portable" is not a reason of allowing unfixed cables. Before I started my work, I screwed all cables on the AI output. Please ensure that cables are screwed on the front/rear panels.
The speaker seems to emit a popping sound when IO chassis is ON/OFF. (I haven't check a situation when AI chassis is ON/OFF. And also, it may emit when the real-time models are launched up properly though they cannot be launched now.) Anyway, I thought my heart stop beating. It might be better to stop the speaker amp by corresponding persons before starting maintenance works or to share for maintainers the procedure to stop/re-start the speaker amp.