VIS (IY)
satoru.ikeda - 17:01 Tuesday 23 March 2021 (16307) Print this report
Comment to Connection of release sensors to DGS (16249)

[Ikeda, Nakagaki-san]

BIO cable connection survey

Conclusion :
BIO4 RightB was confirmed to match the free number CBI(O)_H32_C4 in the model file.

Contents :
Investigated the BIO cable connection of IYV.
BIO is assigned from No.1.
I checked inside the I/O chassis and it was the same.

Below is the list of cable names.

White Cable Label Black Cable Label  
IP-F0 B-OUT CN A BIO1 Left A  
IP-F0 B-IN CN A BIO1 Right A  
GAS B-OUT CN B BIO1 Left B  
GAS B-IN CN B BIO1 Right B  
MNH B-OUT MNH B-OUT BIO2 Left A  
MNH B-IN MNH B-IN BIO2 Right A  
MN IMV B-OUT, MN IMV B-OUT BIO2 Left B  
MN IMV B-IN MN IMV B-IN BIO2 Right B  
IMH B-OUT IMH B-Out BIO3 Left A  
IMH B-IN CN A BIO3 Right A  
IM Dump B-OUT CN B BIO3 Left B  
IM Dump B-IN CN B BIO3 Right B  
TM B-OUT CN A BIO4 Left A  
TM B-IN TM B-IN BIO4 Right A  
Blank B-OUT Blank B-OUT BIO4 Left B not connected
Blank B-IN Blank B-IN BIO4 Right B not connected
BFV B-OUT CN A BIO5 Left A  
BFV B-IN, BFV B-IN BIO5 Right A  
BFH B-OUT BFH B-OUT BIO5 Left B  
BFH B-IN BFH B-IN BIO5 Right B  

 

Check procedure
 K1:VIS-ITMY_BIO_CDCTRL_NOTUSE_WD_RESET OFF->ON
 Verify that K1:VIS-ITMY_BIO_CDCTRL_NOTUSE_DIO_OUT is set to 0 to 65536.

 On the model, In17 (starting at 1) = Binary IO Checker bord, I confirmed that No.16 (starting at 0) is ON (LED lights up).
 I confirmed that the LED turns off when I set it to OFF.

Images attached to this comment
Non-image files attached to this comment