Since the rebooter is connected to the UPS, there is also a suspicion that something might be wrong with the UPS.
>So This Tuesday or Thursday seems to be a good day for recovering TCam (though I'm not sure a detailed work plan on this Tuesday and Thursday yet).
I agree.
I heard from Kimura-san that a battery alarm has been triggered on the UPS around the EYA chamber.
It might to be a UPS related to the EYA Tcam server.
It is unclear at this point whether it is related to the current trouble.
The replacement battery arrived last week and is ready to be installed.
With Satoru Ikeda
Summary:
On-site investigation revealed that the connectivity issue of the EYA TCam server was caused by a faulty UPS. We removed the UPS and connected the rebooter directly to a 100 VAC outlet, which successfully restored the EYA TCam functionality.
Details:
We physically visited the EYA booth to inspect the UPS and server setup.
The UPS showed no visual indicators or alarm sounds.
We confirmed that the UPS input power was normal (100 VAC present).
We removed the UPS from the setup and attempted a reset with the connected load (rebooter) disconnected, but there was no reaction from the UPS—no LEDs, no sound.
Based on this, we judged that the UPS was faulty and did not proceed with battery replacement.
We brought the UPS back to Mozumi for further inspection.
The rebooter (to which the EY TCam server is connected) was plugged directly into a 100 VAC outlet.
After power-on, the TCam server booted normally. We verified that TCam image capture was functional.
Next Steps:
The UPS has alreadly be moved to Mozumi. We will check it later but, it is likely that it needs to be replaced.
Time stamp:
0948: Entered the tunnel.
0951: Entered center front room
0951: Entered center experimental area
0955: Entered Yarm
1011: Entered Yend
1051: Out from Yend
1108: Entered center experimental area
1112: Entered parking area at center
1115: Went out tunnel and closed the shutter of the tunnel entrance.