masayuki.nakano - 0:14 Friday 16 June 2017 (2935) Print this report
PRM, IOO rack power supply
[Kamiizumi, Tomura, Shimode, Nakano]

Recently we had some trouble about TTFSS servo circuit and AEL look around the power supply. In PSL room, we found that the DC 18V and 24V power supply dropped the voltage. (18V-> 16.5-17.2V, 24V->22-23V)

And also, when TTFSS servo was turned on, a DC power supply for prm and ioo racks reached current limit.
 
So the current limit of those power supply was increased to 16A from 10A. And also the voltage for those are increased so that the prm rack 18V tap supply exactly 18V. The picture is current setup of those power supply(first and second are the 18V and others are 24V power supply)